Data center

Cutting-edge and highly customized solutions, part of the market's broadest portfolio, tailored to meet the specific challenges of data centers. Supported by 9 production plants, streamlined processes guarantee rapid delivery and minimal downtime, to keep project execution perfectly on schedule.

By delivering comprehensive turnkey solutions, from seamless installation to expert ongoing support, every aspect of the infrastructure is managed, providing the complete peace of mind needed to focus entirely on core business operations.

Data center

Power solution for Italy’s largest data center campus

Project

Pramac has developed a brand new project of 8 GCW1780P generators and 1  GCW875P generator specifically designed for the data processing center of one of the most important Italian web service companies, Aruba. The generator sets have been built according to the ANSI TIA 942-A certification rating 4 declaring DCC power. The generators have been designed and built according to specific characteristics and with DCC-calibrated engines, with the aim of contributing to the data center’s ANSI TIA 942-A certification. They have been equipped with a customized enclosure solution, double redundant starting system, an automatic fire extinguisher system with CO2 gas and a fuel polishing system. AD HOC solutions have been studied specifically for panels positioning and fuel pipes connections.

Contact Us

Location Ponte San Pietro
Country Italy (IT)
Size range 10000-15000 kW

Key features

GCW1780P

  • Power DCC 1700 kVA
  • Frequency 50 Hz
  • Voltage 400 V
  • Power factor 0,8
  • Engine PERKINS model 4012-46TAG3A
  • Double redundant starting system with double battery pack
  • Alternator MECCALTE model ECO46 1,5S
  • Soundproof enclosure noise level 70 +/-3 dB(A) @ 7 m
  • Motorized louvers
  • Automatic panel
  • Circuit breaker on genset
  • Incorporated double wall fuel tank 500 L
  • Double redundant automatic fuel transfer pump
  • Automatic fire extinguisher system with CO2 gas installed on the soundproof enclosure
  • Engine water preheating system
  • Fuel filter with water separator
  • Fuel polishing system 

GCW875P

  • Power DCC 807 kVA
  • Frequency 50 Hz
  • Voltage 400 V
  • Power factor 0,8
  • Engine PERKINS model 4006-23TAG3A
  • Double redundant starting system with double battery pack

PRAMAC_Aruba_-Power-generators_data-center_Ponte-San-Pietro_Bergamo_0x600.jpg